To size a seal pot for a dual mechanical seal, start from the API 682 minimum liquid volume for the shaft diameter, then check the pot against the refill interval, its vapor space and the seal’s heat load.
The steps apply to the reservoir of a Plan 52 or Plan 53A system. Plans 53B and 53C hold the barrier fluid in an accumulator whose size API 682 sets by shaft diameter; see seal pot pressure for Plans 53A, 53B and 53C.
Step 1: Start From the API 682 Minimum Volume
Unless the purchaser specifies otherwise, API 682 (4th edition) requires a seal pot to hold at least 12 L (3 US gal) of liquid at the normal liquid level (NLL) for shaft diameters of 60 mm (2.5 in.) and smaller, and at least 20 L (5 US gal) for shaft diameters larger than 60 mm.
Step 2: Check the Working Volume Against the Refill Interval
The 4th edition of API 682 adds a time test to the fixed volumes: the pot’s working volume must last at least 28 days of operation without adding barrier or buffer fluid. The working volume is the liquid between the NLL and the low-level alarm (LLA).
Days between refills = working volume (cc) ÷ seal leakage (cc per day)
Take the leakage rate from the seal maker for your seal and duty. As a reference, typical leakage from a pressurized dual seal on a Plan 53 pot is about 2.5 cc a day.
Step 3: Leave Room for Vapor Space
The vapor space above the NLL must be at least equal to the liquid volume between the NLL and the LLA point. API 682 sets this, together with an NLL at least 150 mm (6 in.) above the LLA.
On a vertical pot of uniform diameter, the rule is met when the space above the NLL is at least as tall as the NLL-to-LLA band.
Step 4: Check the Heat Load
Check the heat load separately from volume: get the heat the seal puts into the barrier fluid from the seal maker, and confirm the pot’s cooling coil removes it.
The heat load is the face heat of the seal plus heat soaking into the barrier fluid from the process. Heat soak can become significant at process temperatures above about 150 °C (302 °F).
The maximum cooling capacity of a coil-cooled Plan 52 or 53A pot is roughly 6 to 8 kW, with 1 to 3 gpm of cooling water through the coil in most applications. A heat load above that capacity calls for Plan 53B or Plan 54, whose systems reach up to 36 kW of cooling.
The barrier fluid changes what the same coil removes. A coil rating quoted for water overstates what the pot removes with an oil barrier fluid.
The cooling must also keep the barrier fluid’s temperature rise across the loop within 15 °F for water-based, diesel or kerosene barrier fluids, and within 30 °F for mineral or synthetic oils.
An external cooler can replace the coil, and where the heat load is very small, so can finned tubing. Air cooling is usually restricted to outdoor installations.
Sizing a Pot Outside API 682
For a pump outside API 682, size the pot at one gallon per inch of shaft diameter, with a minimum of 2 gallons. This is the Fluid Sealing Association’s guideline for Plan 53 pots.
The checks of Steps 2 and 4 still apply to a non-API pot.